Smart SF6 Sensor
NDIR SF6 Sensor 10 years life for SF6 Gas Leakage detection.
- RSS-SF6 is Non Dispersive Infrared (NDIR) gas sensor for ambient air monitoring using dual wavelength technology. Especially designed for the analysis of SF6 leakage, quality and purity inside gas insulated switchgears (GIS).
- RSS-SF6 sensor has long term stability, repeatability and reliable performance and high-precision and easy to calibrate
- Modbus ASCII or RTU data communication offer a variety of options to connect the RSS-SF6 sensor to a controller.
- Technical parameter
Measurement principle: Dual wavelength, Non Dispersive Infra-Red (NDIR),
Measurement range: 0-50/1000/1500ppm
Gas supply: by diffusion (atmospheric pressure)
Warm-up time: < 2 minutes (start-up time)
< 11 minutes (fade in finished)
< 30 minutes (full specification)
Measuring response
Response time (t90): appr. 60 s
Digital resolution (@ zero): 1 ppm
Repeatability: ≤ ± 15 ppm
Linearity error (straight line deviation): ≤ ± 20 ppm
Long term stability (span): ≤ ± 30 ppm over 12 month period
Long term stability (zero): ≤ ± 25 ppm over 12 month period
Influence of T and P
Temp. dependence (zero): ≤ ± 1.5 ppm per °C
Temp. dependence (span): ≤ ± 3 ppm per °C
Pressure dependence: ± 0-100 % of measurement value / hPa
Electrical inputs and outputs
Supply voltage: 6.5 V-9 V DC
Supply current (peak): < 140 mA
Inrush current: < 600 mA
Average power consumption: < 800 mW
Output signal: RS 485, 4-20mA
Climatic conditions
Operating temperature: -20°C + 40 °C
Storage temperature: -20°C + 60 °C Air pressure: 800-1150 hPa
Ambient humidity: 0-95 % relative humidity (not condensing)
Typical values related to 1013 hPa and 22 °C for dry (not condensing) and clean sample gas. Stated values exclude calibration gas tolerance.